What are the types of fire extinguisher?
Australia has six types of portable fire extinguisher. Every cylinder is red, and a coloured band shows what is inside: water (no band), foam (blue), dry chemical powder (white), carbon dioxide (black), wet chemical (oatmeal) and vaporising liquid (yellow).
In Australia every extinguisher is red; the coloured band tells you what is inside.
| Type | Band colour | Fire classes | Typical use |
|---|---|---|---|
| Water | Red (no band) | A | Paper, wood, textiles |
| Foam | Blue | A, B | Flammable liquids, workshops |
| Dry chemical powder (ABE) | White | A, B, C, E | General purpose; vehicles, plant rooms |
| Carbon dioxide (CO2) | Black | B, E | Electrical switchboards, server rooms |
| Wet chemical | Oatmeal | A, F | Commercial kitchens, deep fryers |
| Vaporising liquid | Yellow | A, B, C, E | Clean agent for electronics |
What is a fire extinguisher class?
A fire extinguisher class is a letter that names the kind of fuel that is burning, and every extinguisher label lists the classes it is rated for. Under AS/NZS 1850 Australia uses six classes. Match the class of the likely fire to the extinguisher before an emergency, not during one.
- Class A: ordinary combustibles. Wood, paper, cardboard, textiles, plastics and rubber. Use water, foam, ABE powder, wet chemical or vaporising liquid.
- Class B: flammable and combustible liquids. Petrol, diesel, solvents, paints and lubricating oils (not cooking oils). Use foam, powder, CO2 or vaporising liquid. Water spreads a burning liquid.
- Class C: flammable gases. LPG, natural gas, acetylene and hydrogen. Isolate the gas supply first, then use ABE powder or a vaporising liquid unit rated for Class C.
- Class D: combustible metals. Magnesium, titanium, sodium and fine aluminium swarf or powder. Use only a specialist Class D powder; water can make a metal fire explode.
- Class E: energised electrical equipment. Switchboards, motors, computers and chargers. Use CO2, powder or vaporising liquid. Once the power is isolated, the fire is treated as whatever is still burning, usually Class A or B.
- Class F: cooking oils and fats. Deep fryers and commercial cooktops. Use wet chemical or a fire blanket. Water on burning oil causes a violent flare-up.
Never use water or foam on Class E or F fires.
How do you read a fire extinguisher rating?
The rating on the label combines numbers and class letters, for example 3A:40B:E. The number in front of a letter shows the size of the standard test fire the extinguisher put out for that class, so a higher number means more firefighting capacity. A letter shown on its own, such as E, means the extinguisher is suitable for that class without a size rating. Compare ratings, not just cylinder sizes, when choosing between two units of the same type.
How do fire classes differ in Australia, the US and the UK?
The letters change by country. The United States (NFPA 10) uses A, B, C, D and K: B covers flammable liquids and gases, C is energised electrical equipment and K is cooking oils. The UK and Europe (EN 2) use A, B, C, D and F, with no letter for electrical fires. Colours differ too: UK extinguishers are red with a coloured panel, where blue means powder and cream means foam, while in Australia blue means foam. Check which standard a label is written to before matching a type to a hazard.
Which fire extinguisher do you need?
AS 2444 sets how extinguishers are selected and located: matched to the hazards present, within easy reach of exits and travel paths, mounted with the handle between 1.0 and 1.2 m from the floor, with a location sign visible from the approach. Typical choices by area:
- Offices and general areas: water or ABE powder near exits, with CO2 beside server and communications rooms.
- Workshops and warehouses: ABE powder as the general unit, CO2 near switchboards and foam where fuels and solvents are stored.
- Forklift LPG cylinders and gas stores: ABE powder, because it covers Class C.
- Commercial kitchens: wet chemical and a fire blanket beside the fryers.
- Machining of magnesium or titanium: Class D powder at the machine.
- Vehicles and mobile plant: a vehicle-mounted ABE powder unit.
How often are fire extinguishers inspected?
AS 1851 requires a six-monthly inspection of every portable extinguisher (pressure gauge, seal and pin, hose, body damage, signage, access, service tag) and a pressure test and refill at five-year intervals (hydrostatic test for CO2 units every ten years). The service tag on the cylinder records each check. Expired or discharged units are tagged out and replaced immediately.
How do you use a fire extinguisher?
Only attempt a fire that is small, with an exit behind you, after the alarm has been raised and once you have checked the label matches the class of fire. Then follow PASS:
- Pull the pin and break the seal.
- Aim the nozzle or horn at the base of the fire, not the flames.
- Squeeze the handle to discharge.
- Sweep side to side across the base until the fire is out, then watch for re-ignition.
If the fire is not going out, leave, close the door behind you and wait for the fire brigade.
Fire safety inside daily management
The six-monthly check is a contractor's job; the monthly visual check (gauge in the green, pin and seal intact, access clear, sign visible) belongs on the area's safety checklist and 5S audit. A missing or obstructed extinguisher found on a gemba walk is a safety action with an owner that day, and the finding is reviewed at the huddle, not filed until the next service visit.